Misplaced Pages

Nesjavellir Geothermal Power Station

Article snapshot taken from Wikipedia with creative commons attribution-sharealike license. Give it a read and then ask your questions in the chat. We can research this topic together.

The Nesjavellir Geothermal Power Station ( Icelandic : Nesjavallavirkjun , Icelandic pronunciation: [ˈnɛːsjaˌvatlaˌvɪr̥cʏn] ) is the second-largest geothermal power station in Iceland . The facility is located 177 m (581 ft) above sea level in the southwestern part of the country, near Þingvellir National Park and the Hengill mountain range , about 30 km east of central Reykjavík . The power station is owned and operated by ON Power .

#171828

59-626: Plans for utilizing the Nesjavellir [ˈnɛːsjaˌvɛtlɪr̥] area for geothermal power and water heating began in 1947, when boreholes were drilled to evaluate the area's potential for power generation. Research continued from 1965 to 1986. In 1987, construction of the plant began, and the cornerstone was laid in May 1990. The station produces approximately 120 MW of electrical power; it also delivers around 1,100 litres (290 US gal) of hot water 82–85 °C (180–185 °F) per second - with

118-558: A light bulb with a power rating of 100 W is turned on for one hour, the energy used is 100 watt hours (W·h), 0.1 kilowatt hour, or 360  kJ . This same amount of energy would light a 40-watt bulb for 2.5 hours, or a 50-watt bulb for 2 hours. Power stations are rated using units of power, typically megawatts or gigawatts (for example, the Three Gorges Dam in China is rated at approximately 22 gigawatts). This reflects

177-624: A heating capacity of 300 MWt, serving around half of the space heating and hot water needs of the Capital Region , the rest provided by lower temperature fields and the Hellisheiði Geothermal CHP plant . This article about an Icelandic building or structure is a stub . You can help Misplaced Pages by expanding it . This article about renewable energy plants is a stub . You can help Misplaced Pages by expanding it . Megawatt The watt (symbol: W )

236-405: A higher apparent power and higher losses for the same amount of active power. The power factor is 1.0 when the voltage and current are in phase . It is zero when the current leads or lags the voltage by 90 degrees. When the voltage and current are 180 degrees out of phase, the power factor is negative one, and the load is feeding energy into the source (an example would be a home with solar cells on

295-463: A measure of control to system operators over reactive power flow and thus voltage. Because these devices have opposite effects on the phase angle between voltage and current, they can be used to "cancel out" each other's effects. This usually takes the form of capacitor banks being used to counteract the lagging power factor caused by induction motors. Transmission connected generators are generally required to support reactive power flow. For example, on

354-452: A perfect capacitor or inductor, there is no net power transfer; so all power is reactive. Therefore, for a perfect capacitor or inductor: where X {\displaystyle X} is the reactance of the capacitor or inductor. If X {\displaystyle X} is defined as being positive for an inductor and negative for a capacitor, then the modulus signs can be removed from S and X and get Instantaneous power

413-412: A period of one year: equivalent to approximately 114 megawatts of constant power output. The watt-second is a unit of energy, equal to the joule . One kilowatt hour is 3,600,000 watt seconds. While a watt per hour is a unit of rate of change of power with time, it is not correct to refer to a watt (or watt-hour) as a watt per hour. Real power In an electric circuit, instantaneous power

472-484: A purely resistive load, real power can be simplified to: R denotes resistance (units in ohms, Ω) of the load. Reactive power (units in volts-amps-reactive, var) is derived as: For a purely reactive load, reactive power can be simplified to: where X denotes reactance (units in ohms, Ω) of the load. Combining, the complex power (units in volt-amps, VA) is back-derived as and the apparent power (units in volt-amps, VA) as These are simplified diagrammatically by

531-417: A quantity that depends on the reference angle chosen for V or I, but defining S as V I* results in a quantity that doesn't depend on the reference angle and allows to relate S to P and Q. Other forms of complex power (units in volt-amps, VA) are derived from Z , the load impedance (units in ohms, Ω). Consequentially, with reference to the power triangle, real power (units in watts, W) is derived as: For

590-480: A shunt capacitor is installed close to the load itself. This allows all reactive power needed by the load to be supplied by the capacitor and not have to be transferred over the transmission lines. This practice saves energy because it reduces the amount of energy that is required to be produced by the utility to do the same amount of work. Additionally, it allows for more efficient transmission line designs using smaller conductors or fewer bundled conductors and optimizing

649-433: A source and a linear time-invariant load, both the current and voltage are sinusoidal at the same frequency. If the load is purely resistive , the two quantities reverse their polarity at the same time. Hence, the instantaneous power, given by the product of voltage and current, is always positive, such that the direction of energy flow does not reverse and always is toward the resistor. In this case, only active power

SECTION 10

#1732782843172

708-541: A turbine, which generates 648 MW e (i.e. electricity). Other SI prefixes are sometimes used, for example gigawatt electrical (GW e ). The International Bureau of Weights and Measures , which maintains the SI-standard, states that further information about a quantity should not be attached to the unit symbol but instead to the quantity symbol (e.g., P th = 270 W rather than P = 270 W th ) and so these unit symbols are non-SI. In compliance with SI,

767-495: A unit of time, namely 1 J/s. In this new definition, 1 absolute watt = 1.00019 international watts. Texts written before 1948 are likely to be using the international watt, which implies caution when comparing numerical values from this period with the post-1948 watt. In 1960, the 11th General Conference on Weights and Measures adopted the absolute watt into the International System of Units (SI) as

826-424: A very interesting result. However, the time average of a function of the form cos( ωt + k ) is zero provided that ω is nonzero. Therefore, the only product terms that have a nonzero average are those where the frequency of voltage and current match. In other words, it is possible to calculate active (average) power by simply treating each frequency separately and adding up the answers. Furthermore, if voltage of

885-449: Is 45.6°. The power factor is cos(45.6°) = 0.700 . The apparent power is then: 700 W / cos(45.6°) = 1000 VA . The concept of power dissipation in AC circuit is explained and illustrated with the example. For instance, a power factor of 0.68 means that only 68 percent of the total current supplied (in magnitude) is actually doing work; the remaining current does no work at the load. Power Factor

944-642: Is an important source of reactive power in the above power balance equation, which is generated by the capacitative nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day. To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, static VAR compensators and voltage control circuits. While active power and reactive power are well defined in any system,

1003-442: Is defined as: where v ( t ) {\displaystyle v(t)} and i ( t ) {\displaystyle i(t)} are the time-varying voltage and current waveforms. This definition is useful because it applies to all waveforms, whether they are sinusoidal or not. This is particularly useful in power electronics, where non-sinusoidal waveforms are common. In general, engineers are interested in

1062-437: Is known as instantaneous active power, and its time average is known as active power or real power . The portion of instantaneous power that results in no net transfer of energy but instead oscillates between the source and load in each cycle due to stored energy is known as instantaneous reactive power, and its amplitude is the absolute value of reactive power . In a simple alternating current (AC) circuit consisting of

1121-733: Is named after the Scottish inventor James Watt . The unit name was proposed by C. William Siemens in August 1882 in his President's Address to the Fifty-Second Congress of the British Association for the Advancement of Science . Noting that units in the practical system of units were named after leading physicists, Siemens proposed that watt might be an appropriate name for a unit of power. Siemens defined

1180-449: Is no net transfer of energy to the load; however, electrical power does flow along the wires and returns by flowing in reverse along the same wires. The current required for this reactive power flow dissipates energy in the line resistance, even if the ideal load device consumes no energy itself. Practical loads have resistance as well as inductance, or capacitance, so both active and reactive powers will flow to normal loads. Apparent power

1239-402: Is often expressed in volt-amperes (VA) since it is the product of RMS voltage and RMS current . The unit for reactive power is var, which stands for volt-ampere reactive . Since reactive power transfers no net energy to the load, it is sometimes called "wattless" power. It does, however, serve an important function in electrical grids and its lack has been cited as a significant factor in

SECTION 20

#1732782843172

1298-413: Is the cosine of the phase angle ( φ {\displaystyle \varphi } ) between the current and voltage sinusoidal waveforms. Equipment data sheets and nameplates will often abbreviate power factor as " cos ⁡ ϕ {\displaystyle \cos \phi } " for this reason. Example: The active power is 700 W and the phase angle between voltage and current

1357-575: Is the product of the RMS values of voltage and current. Apparent power is taken into account when designing and operating power systems, because although the current associated with reactive power does no work at the load, it still must be supplied by the power source. Conductors, transformers and generators must be sized to carry the total current, not just the current that does useful work. Insufficient reactive power can depress voltage levels on an electrical grid and, under certain operating conditions, collapse

1416-523: Is the rate at which electrical work is performed when a current of one ampere (A) flows across an electrical potential difference of one volt (V), meaning the watt is equivalent to the volt-ampere (the latter unit, however, is used for a different quantity from the real power of an electrical circuit). 1   W = 1   V ⋅ A . {\displaystyle \mathrm {1~W=1~V{\cdot }A} .} Two additional unit conversions for watt can be found using

1475-452: Is the time rate of flow of energy past a given point of the circuit. In alternating current circuits, energy storage elements such as inductors and capacitors may result in periodic reversals of the direction of energy flow. Its SI unit is the watt . The portion of instantaneous power that, averaged over a complete cycle of the AC waveform , results in net transfer of energy in one direction

1534-472: Is the unit of power or radiant flux in the International System of Units (SI), equal to 1 joule per second or 1 kg⋅m ⋅s . It is used to quantify the rate of energy transfer . The watt is named in honor of James Watt (1736–1819), an 18th-century Scottish inventor , mechanical engineer , and chemist who improved the Newcomen engine with his own steam engine in 1776. Watt's invention

1593-440: Is transferred. If the load is purely reactive , then the voltage and current are 90 degrees out of phase. For two quarters of each cycle, the product of voltage and current is positive, but for the other two quarters, the product is negative, indicating that on average, exactly as much energy flows into the load as flows back out. There is no net energy flow over each half cycle. In this case, only reactive power flows: There

1652-470: Is very important in Power sector substations. Form the national grid the sub sectors are required to have minimum amount of power factor. Otherwise there are many loss. Mainly the required vary around 0.90 to 0.96 or more. Better the power factor less the loss. In a direct current circuit, the power flowing to the load is proportional to the product of the current through the load and the potential drop across

1711-507: The Northeast blackout of 2003 . Understanding the relationship among these three quantities lies at the heart of understanding power engineering. The mathematical relationship among them can be represented by vectors or expressed using complex numbers , S  =  P  +  j Q (where j is the imaginary unit ). The formula for complex power (units: VA) in phasor form is: where V denotes voltage in phasor form, with

1770-545: The United Kingdom transmission system, generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation: The " system gain "

1829-470: The above equation and Ohm's law . 1   W = 1   V 2 / Ω = 1   A 2 ⋅ Ω , {\displaystyle \mathrm {1~W=1~V^{2}/\Omega =1~A^{2}{\cdot }\Omega } ,} where ohm ( Ω {\displaystyle \Omega } ) is the SI derived unit of electrical resistance . The watt

Nesjavellir Geothermal Power Station - Misplaced Pages Continue

1888-430: The active power averaged over a period of time, whether it is a low frequency line cycle or a high frequency power converter switching period. The simplest way to get that result is to take the integral of the instantaneous calculation over the desired period: This method of calculating the average power gives the active power regardless of harmonic content of the waveform. In practical applications, this would be done in

1947-430: The adjacent diagram (called a power triangle). In the diagram, P is the active power, Q is the reactive power (in this case positive), S is the complex power and the length of S is the apparent power. Reactive power does not do any work, so it is represented as the imaginary axis of the vector diagram. Active power does do work, so it is the real axis. The unit for power is the watt (symbol: W). Apparent power

2006-430: The amplitude as RMS , and I denotes current in phasor form, with the amplitude as RMS. Also by convention, the complex conjugate of I is used, which is denoted I ∗ {\displaystyle I^{*}} (or I ¯ {\displaystyle {\overline {I}}} ), rather than I itself. This is done because otherwise using the product V I to define S would result in

2065-446: The capacitor structure. In an AC network, the voltage across a capacitor is constantly changing. The capacitor opposes this change, causing the current to lead the voltage in phase. Capacitors are said to "source" reactive power, and thus to cause a leading power factor. Induction machines are some of the most common types of loads in the electric power system today. These machines use inductors , or large coils of wire to store energy in

2124-406: The currents flowing through the capacitor and the inductor tend to cancel rather than add. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors (or inductors) are inserted in a circuit to partially compensate for reactive power 'consumed' ('generated') by the load. Purely capacitive circuits supply reactive power with the current waveform leading

2183-471: The definition of apparent power for unbalanced polyphase systems is considered to be one of the most controversial topics in power engineering. Originally, apparent power arose merely as a figure of merit. Major delineations of the concept are attributed to Stanley 's Phenomena of Retardation in the Induction Coil (1888) and Steinmetz 's Theoretical Elements of Engineering (1915). However, with

2242-448: The design of transmission towers. Stored energy in the magnetic or electric field of a load device, such as a motor or capacitor, causes an offset between the current and the voltage waveforms. A capacitor is a device that stores energy in the form of an electric field. As current is driven through the capacitor, charge build-up causes an opposing voltage to develop across the capacitor. This voltage increases until some maximum dictated by

2301-557: The development of three phase power distribution, it became clear that the definition of apparent power and the power factor could not be applied to unbalanced polyphase systems . In 1920, a "Special Joint Committee of the AIEE and the National Electric Light Association" met to resolve the issue. They considered two definitions. that is, the arithmetic sum of the phase apparent powers; and that is,

2360-424: The digital domain, where the calculation becomes trivial when compared to the use of rms and phase to determine active power: Since an RMS value can be calculated for any waveform, apparent power can be calculated from this. For active power it would at first appear that it would be necessary to calculate many product terms and average all of them. However, looking at one of these product terms in more detail produces

2419-515: The energy company Ørsted A/S uses the unit megawatt for produced electrical power and the equivalent unit megajoule per second for delivered heating power in a combined heat and power station such as Avedøre Power Station . When describing alternating current (AC) electricity, another distinction is made between the watt and the volt-ampere . While these units are equivalent for simple resistive circuits , they differ when loads exhibit electrical reactance . Radio stations usually report

Nesjavellir Geothermal Power Station - Misplaced Pages Continue

2478-443: The form of a magnetic field. When a voltage is initially placed across the coil, the inductor strongly resists this change in a current and magnetic field, which causes a time delay for the current to reach its maximum value. This causes the current to lag behind the voltage in phase. Inductors are said to "sink" reactive power, and thus to cause a lagging power factor. Induction generators can source or sink reactive power, and provide

2537-523: The load. The power that happens because of a capacitor or inductor is called reactive power. It happens because of the AC nature of elements like inductors and capacitors. Energy flows in one direction from the source to the load. In AC power, the voltage and current both vary approximately sinusoidally. When there is inductance or capacitance in the circuit, the voltage and current waveforms do not line up perfectly. The power flow has two components – one component flows from source to load and can perform work at

2596-530: The load; the other portion, known as "reactive power", is due to the delay between voltage and current, known as phase angle, and cannot do useful work at the load. It can be thought of as current that is arriving at the wrong time (too late or too early). To distinguish reactive power from active power, it is measured in units of " volt-amperes reactive ", or var. These units can simplify to watts but are left as var to denote that they represent no actual work output. Energy stored in capacitive or inductive elements of

2655-459: The magnitude of total three-phase complex power. The 1920 committee found no consensus and the topic continued to dominate discussions. In 1930, another committee formed and once again failed to resolve the question. The transcripts of their discussions are the lengthiest and most controversial ever published by the AIEE. Further resolution of this debate did not come until the late 1990s. A new definition based on symmetrical components theory

2714-457: The mains supply is assumed to be a single frequency (which it usually is), this shows that harmonic currents are a bad thing. They will increase the RMS current (since there will be non-zero terms added) and therefore apparent power, but they will have no effect on the active power transferred. Hence, harmonic currents will reduce the power factor. Harmonic currents can be reduced by a filter placed at

2773-460: The maximum power output it can achieve at any point in time. A power station's annual energy output, however, would be recorded using units of energy (not power), typically gigawatt hours. Major energy production or consumption is often expressed as terawatt hours for a given period; often a calendar year or financial year. One terawatt hour of energy is equal to a sustained power delivery of one terawatt for one hour, or approximately 114 megawatts for

2832-420: The network (a blackout ). Another consequence is that adding the apparent power for two loads will not accurately give the total power unless they have the same phase difference between current and voltage (the same power factor ). Conventionally, capacitors are treated as if they generate reactive power, and inductors are treated as if they consume it. If a capacitor and an inductor are placed in parallel, then

2891-483: The network gives rise to reactive power flow. Reactive power flow strongly influences the voltage levels across the network. Voltage levels and reactive power flow must be carefully controlled to allow a power system to be operated within acceptable limits. A technique known as reactive compensation is used to reduce apparent power flow to a load by reducing reactive power supplied from transmission lines and providing it locally. For example, to compensate an inductive load,

2950-406: The positive sequence voltage phasor, and I + {\displaystyle I^{+}} denotes the positive sequence current phasor. A perfect resistor stores no energy; so current and voltage are in phase. Therefore, there is no reactive power and P = S {\displaystyle P=S} (using the passive sign convention ). Therefore, for a perfect resistor For

3009-488: The power of their transmitters in units of watts, referring to the effective radiated power . This refers to the power that a half-wave dipole antenna would need to radiate to match the intensity of the transmitter's main lobe . The terms power and energy are closely related but distinct physical quantities. Power is the rate at which energy is generated or consumed and hence is measured in units (e.g. watts) that represent energy per unit time . For example, when

SECTION 50

#1732782843172

3068-449: The power triangle. The ratio of active power to apparent power in a circuit is called the power factor . For two systems transmitting the same amount of active power, the system with the lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the load. These higher currents produce higher losses and reduce overall transmission efficiency. A lower power factor circuit will have

3127-408: The roof that feed power into the power grid when the sun is shining). Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle of current with respect to voltage. Voltage is designated as the base to which current angle is compared, meaning that current is thought of as either "leading" or "lagging" voltage. Where the waveforms are purely sinusoidal, the power factor

3186-569: The unit of power. In the electric power industry , megawatt electrical ( MWe or MW e ) refers by convention to the electric power produced by a generator, while megawatt thermal or thermal megawatt (MWt, MW t , or MWth, MW th ) refers to thermal power produced by the plant. For example, the Embalse nuclear power plant in Argentina uses a fission reactor to generate 2,109 MW t (i.e. heat), which creates steam to drive

3245-570: The unit within the existing system of practical units as "the power conveyed by a current of an Ampère through the difference of potential of a Volt". In October 1908, at the International Conference on Electric Units and Standards in London, so-called international definitions were established for practical electrical units. Siemens' definition was adopted as the international watt. (Also used: 1 A × 1 Ω.) The watt

3304-443: The voltage waveform by 90 degrees, while purely inductive circuits absorb reactive power with the current waveform lagging the voltage waveform by 90 degrees. The result of this is that capacitive and inductive circuit elements tend to cancel each other out. Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to differentiate between them): These are all denoted in

3363-420: Was defined as equal to 10 units of power in the practical system of units. The "international units" were dominant from 1909 until 1948. After the 9th General Conference on Weights and Measures in 1948, the international watt was redefined from practical units to absolute units (i.e., using only length, mass, and time). Concretely, this meant that 1 watt was defined as the quantity of energy transferred in

3422-694: Was fundamental for the Industrial Revolution . When an object's velocity is held constant at one meter per second against a constant opposing force of one newton , the rate at which work is done is one watt. 1   W = 1   J / s = 1   N ⋅ m / s = 1   k g ⋅ m 2 ⋅ s − 3 . {\displaystyle \mathrm {1~W=1~J{/}s=1~N{\cdot }m{/}s=1~kg{\cdot }m^{2}{\cdot }s^{-3}} .} In terms of electromagnetism , one watt

3481-400: Was proposed in 1993 by Alexander Emanuel for unbalanced linear load supplied with asymmetrical sinusoidal voltages: that is, the root of squared sums of line voltages multiplied by the root of squared sums of line currents. P + {\displaystyle P^{+}} denotes the positive sequence power: V + {\displaystyle V^{+}} denotes

#171828