A control loop is the fundamental building block of control systems in general and industrial control systems in particular. It consists of the process sensor , the controller function, and the final control element (FCE) which controls the process necessary to automatically adjust the value of a measured process variable (PV) to equal the value of a desired set-point (SP).
50-425: A control system manages, commands, directs, or regulates the behavior of other devices or systems using control loops . It can range from a single home heating controller using a thermostat controlling a domestic boiler to large industrial control systems which are used for controlling processes or machines. The control systems are designed via control engineering process. For continuously modulated control,
100-505: A PID controller which means it can generate a full range of output signals anywhere between 0-100%, rather than just an on/off signal. In this example, the value of the PV is always the same as the MV, as they are in series in the pipeline. However, if the feed from the valve was to a tank, and the controller function was to control the level using the fill valve, the PV would be the tank level, and
150-557: A PID controller , can be improved by combining the feedback (or closed-loop control ) of a PID controller with feed-forward (or open-loop) control. Knowledge about the system (such as the desired acceleration and inertia) can be fed forward and combined with the PID output to improve the overall system performance. The feed-forward value alone can often provide the major portion of the controller output. The PID controller primarily has to compensate whatever difference or error remains between
200-463: A Piping and instrumentation diagram , which shows all elements of the process measurement and control based on a process flow diagram . At a detailed level the control loop connection diagram is created to show the electrical and pneumatic connections. This greatly aids diagnostics and repair, as all the connections for a single control function are on one diagram. To aid unique identification of equipment, each loop and its elements are identified by
250-403: A control loop including sensors , control algorithms, and actuators is arranged in an attempt to regulate a variable at a setpoint (SP). An everyday example is the cruise control on a road vehicle; where external influences such as hills would cause speed changes, and the driver has the ability to alter the desired set speed. The PID algorithm in the controller restores the actual speed to
300-416: A dynamical system . Its name comes from the information path in the system: process inputs (e.g., voltage applied to an electric motor ) have an effect on the process outputs (e.g., speed or torque of the motor), which is measured with sensors and processed by the controller; the result (the control signal) is "fed back" as input to the process, closing the loop. In the case of linear feedback systems,
350-430: A feedback controller is used to automatically control a process or operation. The control system compares the value or status of the process variable (PV) being controlled with the desired value or setpoint (SP), and applies the difference as a control signal to bring the process variable output of the plant to the same value as the setpoint. For sequential and combinational logic , software logic , such as in
400-474: A non-feedback controller , is a control loop part of a control system in which the control action ("input" to the system ) is independent of the "process output", which is the process variable that is being controlled. It does not use feedback to determine if its output has achieved the desired goal of the input command or process setpoint . There are many open- loop controls, such as on/off switching of valves, machinery, lights, motors or heaters, where
450-404: A programmable logic controller , is used. Fundamentally, there are two types of control loop: open-loop control (feedforward), and closed-loop control (feedback). In open-loop control, the control action from the controller is independent of the "process output" (or "controlled process variable"). A good example of this is a central heating boiler controlled only by a timer, so that heat
500-576: A thermostat to monitor the building temperature, and feed back a signal to ensure the controller output maintains the building temperature close to that set on the thermostat. A closed-loop controller has a feedback loop which ensures the controller exerts a control action to control a process variable at the same value as the setpoint. For this reason, closed-loop controllers are also called feedback controllers. Fundamentally, there are two types of control loop: open-loop control (feedforward), and closed-loop control (feedback). In open-loop control,
550-417: A timer . The control action is the switching on or off of the boiler. The process variable is the building temperature. This controller operates the heating system for a constant time regardless of the temperature of the building. In a closed-loop control system, the control action from the controller is dependent on the desired and actual process variable. In the case of the boiler analogy, this would utilize
SECTION 10
#1732779777603600-417: A "tagging" system and each element has a unique tag identification. Based on the standards ANSI / ISA S5.1 and ISO 14617 -6, the identifications consist of up to 5 letters. The first identification letter is for the measured value, the second is a modifier, 3rd indicates the passive/readout function, 4th - active/output function, and the 5th is the function modifier. This is followed by loop number, which
650-640: A closed loop control system according to the British Standards Institution is "a control system possessing monitoring feedback, the deviation signal formed as a result of this feedback being used to control the action of a final control element in such a way as to tend to reduce the deviation to zero." A closed-loop controller or feedback controller is a control loop which incorporates feedback , in contrast to an open-loop controller or non-feedback controller . A closed-loop controller uses feedback to control states or outputs of
700-407: A control loop with a single PV input, a control function, and the control output (CO) which modulates the action of the final control element (FCE) to alter the value of the manipulated variable (MV). In this example, a flow control loop is shown, but can be level, temperature, or any one of many process parameters which need to be controlled. The control function shown is an "intermediate type" such as
750-408: A function of the load not just the voltage, and an open-loop controller would be insufficient to ensure repeatable control of the velocity. An example of this is a conveyor system that is required to travel at a constant speed. For a constant voltage, the conveyor will move at a different speed depending on the load on the motor (represented here by the weight of objects on the conveyor). In order for
800-405: A mechanical load under control, more force is required from the actuator. If a velocity loop PID controller is being used to control the speed of the load and command the force being applied by the actuator, then it is beneficial to take the desired instantaneous acceleration, scale that value appropriately and add it to the output of the PID velocity loop controller. This means that whenever the load
850-549: A series of mechanical actuators in the correct sequence to perform a task. For example, various electric and pneumatic transducers may fold and glue a cardboard box, fill it with the product and then seal it in an automatic packaging machine. PLC software can be written in many different ways – ladder diagrams, SFC ( sequential function charts ) or statement lists . On–off control uses a feedback controller that switches abruptly between two states. A simple bi-metallic domestic thermostat can be described as an on-off controller. When
900-461: Is "a control system possessing monitoring feedback, the deviation signal formed as a result of this feedback being used to control the action of a final control element in such a way as to tend to reduce the deviation to zero." An open-loop controller is often used in simple processes because of its simplicity and low cost, especially in systems where feedback is not critical. A typical example would be an older model domestic clothes dryer , for which
950-418: Is "a control system possessing monitoring feedback, the deviation signal formed as a result of this feedback being used to control the action of a final control element in such a way as to tend to reduce the deviation to zero." Likewise; "A Feedback Control System is a system which tends to maintain a prescribed relationship of one system variable to another by comparing functions of these variables and using
1000-493: Is a stepper motor used for control of position. Sending it a stream of electrical pulses causes it to rotate by exactly that many steps, hence the name. If the motor was always assumed to perform each movement correctly, without positional feedback, it would be open-loop control. However, if there is a position encoder, or sensors to indicate the start or finish positions, then that is closed-loop control, such as in many inkjet printers . The drawback of open-loop control of steppers
1050-432: Is a recent framework that provides many open-source hardware devices which can be connected to create more complex data acquisition and control systems. Control loop There are two common classes of control loop: open loop and closed loop. In an open-loop control system, the control action from the controller is independent of the process variable. An example of this is a central heating boiler controlled only by
SECTION 20
#17327797776031100-532: Is an electronic technology that uses fuzzy logic instead of the two-value logic more commonly used in digital electronics . The range of control system implementation is from compact controllers often with dedicated software for a particular machine or device, to distributed control systems for industrial process control for a large physical plant . Logic systems and feedback controllers are usually implemented with programmable logic controllers . The Broadly Reconfigurable and Expandable Automation Device (BREAD)
1150-401: Is applied for a constant time, regardless of the temperature of the building. The control action is the switching on/off of the boiler, but the controlled variable should be the building temperature, but is not because this is open-loop control of the boiler, which does not give closed-loop control of the temperature. In closed loop control, the control action from the controller is dependent on
1200-419: Is being accelerated or decelerated, a proportional amount of force is commanded from the actuator regardless of the feedback value. The PID loop in this situation uses the feedback information to change the combined output to reduce the remaining difference between the process setpoint and the feedback value. Working together, the combined open-loop feed-forward controller and closed-loop PID controller can provide
1250-421: Is no feedback ; no measurement of the system output (the car's speed) is used to alter the control (the throttle position.) As a result, the controller cannot compensate for changes acting on the car, like a change in the slope of the road. In a closed-loop control system , data from a sensor monitoring the car's speed (the system output) enters a controller which continuously compares the quantity representing
1300-401: Is not because this is open-loop control of the boiler, which does not give closed-loop control of the temperature. In closed loop control, the control action from the controller is dependent on the process output. In the case of the boiler analogy this would include a thermostat to monitor the building temperature, and thereby feed back a signal to ensure the controller maintains the building at
1350-401: Is not because this is open-loop control of the boiler, which does not give closed-loop control of the temperature. In closed loop control, the control action from the controller is dependent on the process output. In the case of the boiler analogy this would include a thermostat to monitor the building temperature, and thereby feed back a signal to ensure the controller maintains the building at
1400-430: Is still in use as a programming method for PLCs. Logic controllers may respond to switches and sensors and can cause the machinery to start and stop various operations through the use of actuators . Logic controllers are used to sequence mechanical operations in many applications. Examples include elevators, washing machines and other systems with interrelated operations. An automatic sequential control system may trigger
1450-430: Is that if the machine load is too high, or the motor attempts to move too quickly, then steps may be skipped. The controller has no means of detecting this and so the machine continues to run slightly out of adjustment until reset. For this reason, more complex robots and machine tools instead use servomotors rather than stepper motors, which incorporate encoders and closed-loop controllers . However, open-loop control
1500-441: Is the engine's throttle position which determines how much power the engine delivers. A primitive way to implement cruise control is simply to lock the throttle position when the driver engages cruise control. However, if the cruise control is engaged on a stretch of non-flat road, then the car will travel slower going uphill and faster when going downhill. This type of controller is called an open-loop controller because there
1550-703: Is unique to that loop. For instance, FIC045 means it is the Flow Indicating Controller in control loop 045. This is also known as the "tag" identifier of the field device, which is normally given to the location and function of the instrument. The same loop may have FT045 - which is the flow transmitter in the same loop. For reference designation of any equipment in industrial systems the standard IEC 61346 ( Industrial systems, installations and equipment and industrial products — Structuring principles and reference Open-loop controller In control theory , an open-loop controller , also called
Control system - Misplaced Pages Continue
1600-424: Is very useful and economic for well-defined systems where the relationship between input and the resultant state can be reliably modeled by a mathematical formula. For example, determining the voltage to be fed to an electric motor that drives a constant load, in order to achieve a desired speed would be a good application. But if the load were not predictable and became excessive, the motor's speed might vary as
1650-467: The MV would be the flow to the tank. The controller function can be a discrete controller or a function block in a computerised control system such as a distributed control system or a programmable logic controller . In all cases, a control loop diagram is a very convenient and useful way of representing the control function and its interaction with plant. In practice at a process control level, control loops are normally abbreviated using standard symbols in
1700-410: The control action from the controller is independent of the "process output" (or "controlled process variable"). A good example of this is a central heating boiler controlled only by a timer, so that heat is applied for a constant time, regardless of the temperature of the building. The control action is the switching on/off of the boiler, but the controlled variable should be the building temperature, but
1750-410: The control action from the controller is independent of the "process output" (or "controlled process variable"). A good example of this is a central heating boiler controlled only by a timer, so that heat is applied for a constant time, regardless of the temperature of the building. The control action is the switching on/off of the boiler, but the controlled variable should be the building temperature, but
1800-419: The control of complex continuously varying systems. Basically, a measurement in a fuzzy logic system can be partly true. The rules of the system are written in natural language and translated into fuzzy logic. For example, the design for a furnace would start with: "If the temperature is too high, reduce the fuel to the furnace. If the temperature is too low, increase the fuel to the furnace." Measurements from
1850-520: The control result is known to be approximately sufficient under normal conditions without the need for feedback. The advantage of using open-loop control in these cases is the reduction in component count and complexity. However, an open-loop system cannot correct any errors that it makes or correct for outside disturbances unlike a closed-loop control system . Fundamentally, there are two types of control loop: open-loop control (feedforward), and closed-loop control (feedback). In open-loop control,
1900-400: The conveyor to run at a constant speed, the voltage of the motor must be adjusted depending on the load. In this case, a closed-loop control system would be necessary. Thus there are many open-loop controls, such as switching valves, lights, motors or heaters on and off, where the result is known to be approximately sufficient without the need for feedback. A feed back control system, such as
1950-417: The desired speed in an optimum way, with minimal delay or overshoot , by controlling the power output of the vehicle's engine. Control systems that include some sensing of the results they are trying to achieve are making use of feedback and can adapt to varying circumstances to some extent. Open-loop control systems do not make use of feedback, and run only in pre-arranged ways. Closed-loop controllers have
2000-400: The difference as a means of control." An example of a control system is a car's cruise control , which is a device designed to maintain vehicle speed at a constant desired or reference speed provided by the driver. The controller is the cruise control, the plant is the car, and the system is the car and the cruise control. The system output is the car's speed, and the control itself
2050-703: The following advantages over open-loop controllers: In some systems, closed-loop and open-loop control are used simultaneously. In such systems, the open-loop control is termed feedforward and serves to further improve reference tracking performance. A common closed-loop controller architecture is the PID controller . Logic control systems for industrial and commercial machinery were historically implemented by interconnected electrical relays and cam timers using ladder logic . Today, most such systems are constructed with microcontrollers or more specialized programmable logic controllers (PLCs). The notation of ladder logic
Control system - Misplaced Pages Continue
2100-454: The length of time is entirely dependent on the judgement of the human operator, with no automatic feedback of the dryness of the clothes. For example, an irrigation sprinkler system, programmed to turn on at set times could be an example of an open-loop system if it does not measure soil moisture as a form of feedback. Even if rain is pouring down on the lawn, the sprinkler system would activate on schedule, wasting water. Another example
2150-526: The process output. In the case of the boiler analogy this would include a thermostat to monitor the building temperature, and thereby feed back a signal to ensure the controller maintains the building at the temperature set on the thermostat. A closed loop controller therefore has a feedback loop which ensures the controller exerts a control action to give a process output the same as the "reference input" or "set point". For this reason, closed loop controllers are also called feedback controllers. The definition of
2200-553: The real world (such as the temperature of a furnace) are fuzzified and logic is calculated arithmetic, as opposed to Boolean logic , and the outputs are de-fuzzified to control equipment. When a robust fuzzy design is reduced to a single, quick calculation, it begins to resemble a conventional feedback loop solution and it might appear that the fuzzy design was unnecessary. However, the fuzzy logic paradigm may provide scalability for large control systems where conventional methods become unwieldy or costly to derive. Fuzzy electronics
2250-422: The sensed speed drops below the reference, the difference increases, the throttle opens, and engine power increases, speeding up the vehicle. In this way, the controller dynamically counteracts changes to the car's speed. The central idea of these control systems is the feedback loop , the controller affects the system output, which in turn is measured and fed back to the controller. The accompanying diagram shows
2300-455: The setpoint (SP) and the system response to the open-loop control. Since the feed-forward output is not affected by the process feedback, it can never cause the control system to oscillate, thus improving the system response without affecting stability. Feed forward can be based on the setpoint and on extra measured disturbances. Setpoint weighting is a simple form of feed forward. For example, in most motion control systems, in order to accelerate
2350-402: The speed with the reference quantity representing the desired speed. The difference, called the error, determines the throttle position (the control). The result is to match the car's speed to the reference speed (maintain the desired system output). Now, when the car goes uphill, the difference between the input (the sensed speed) and the reference continuously determines the throttle position. As
2400-437: The temperature in the room (PV) goes below the user setting (SP), the heater is switched on. Another example is a pressure switch on an air compressor. When the pressure (PV) drops below the setpoint (SP) the compressor is powered. Refrigerators and vacuum pumps contain similar mechanisms. Simple on–off control systems like these can be cheap and effective. Fuzzy logic is an attempt to apply the easy design of logic controllers to
2450-399: The temperature set on the thermostat. A closed loop controller therefore has a feedback loop which ensures the controller exerts a control action to give a process output the same as the "reference input" or "set point". For this reason, closed loop controllers are also called feedback controllers. The definition of a closed loop control system according to the British Standards Institution
2500-399: The temperature set on the thermostat. A closed loop controller therefore has a feedback loop which ensures the controller exerts a control action to give a process output the same as the "reference input" or "set point". For this reason, closed loop controllers are also called feedback controllers. The definition of a closed loop control system according to the British Standards Institution