An HVDC converter station (or simply converter station ) is a specialised type of substation which forms the terminal equipment for a high-voltage direct current (HVDC) transmission line. It converts direct current to alternating current or the reverse. In addition to the converter , the station usually contains:

#927072

19-618: Henday Converter Station is an HVDC converter station near Sundance in the Canadian province of Manitoba . The Henday Converter Station is the northern terminus for Manitoba Hydro's Bipole II high voltage direct current (HVDC) transmission system and was built in 1977. It is 42 kilometres northeast of the Radisson Converter Station and is close to the Limestone Generating Station . It

38-410: A large DC potential to earth. Converter transformers can be built as large as 300 Mega volt amperes ( MVA ) as a single unit. It is impractical to transport larger transformers, so when larger ratings are required, several individual transformers are connected together. Either two three-phase units or three single-phase units can be used. With the latter variant only one type of transformer is used, making

57-403: A result, harmonic filters are generally smaller or may be omitted altogether. Beside the harmonic filters, equipment is also provided to eliminate spurious signals in the frequency range of power-line carrier equipment in the range of 30 kHz to 500 kHz. These filters are usually near the alternating current terminal of the static inverter transformer. They consist of a coil which passes

76-423: A single three-phase transformer, or built from three independent single-phase units. An equivalent term is delta-star transformer . Delta-wye transformers are common in commercial, industrial, and high-density residential locations, to supply three-phase distribution systems . An example would be a distribution transformer with a delta primary, running on three 11 kV phases with no neutral or earth required, and

95-415: A spill. Substantial area may be required for overhead transmission lines, but can be reduced if underground cable is used. Delta-wye transformer A delta-wye transformer is a type of three-phase electric power transformer design that employs delta-connected windings on its primary and wye/star connected windings on its secondary. A neutral wire can be provided on wye output side. It can be

114-584: A sufficient range of taps for AC voltage control. Some of the reactive power requirement can be supplied in the harmonic filter components. Voltage sourced converters can generate or absorb reactive as well as real power, and additional reactive power equipment is generally not needed. Harmonic filters are necessary for the elimination of the harmonic waves and for the production of the reactive power at line commutated converter stations. At plants with six pulse line commutated converters, complex harmonic filters are necessary because there are odd numbered harmonics of

133-538: A system was used on the Baltic Cable HVDC project. The converter transformers step up the voltage of the AC supply network. Using a star-to-delta or " wye-delta " connection of the transformer windings, the converter can operate with 12 pulses for each cycle in the AC supply, which eliminates numerous harmonic current components. The insulation of the transformer windings must be specially designed to withstand

152-559: A transmission voltage of 400 kV is approximately 300 x 300 metres (1000 x 1000 feet). Lower-voltage plants may require somewhat less ground area, since less air space clearance would be required around outdoor high-voltage equipment. Converter stations produce acoustic noise. Converter stations can generate serious levels of radio-frequency interference, so include design features to control these emissions. Walls may provide noise protection. As with all AC substations, oil from equipment must be prevented from contaminating ground water in case of

171-666: Is called rectification and conversion from DC to AC is called inversion . The direct current equipment often includes a coil (called a reactor ) that adds inductance in series with the DC line to help smooth the direct current. The inductance typically amounts to between 0.1 H and 1 H. The smoothing reactor can have either an air-core or an iron-core. Iron-core coils look like oil-filled high voltage transformers. Air-core smoothing coils resemble, but are considerably larger than, carrier frequency choke coils in high voltage transmission lines and are supported by insulators . Air coils have

190-550: Is usually installed in a building called the valve hall . Early HVDC systems used mercury-arc valves , but since the mid-1970s, solid state devices such as thyristors have been used. Converters using thyristors or mercury-arc valves are known as line commutated converters . In thyristor-based converters, many thyristors are connected in series to form a thyristor valve, and each converter normally consists of six or twelve thyristor valves. The thyristor valves are usually grouped in pairs or groups of four and can stand on insulators on

209-426: The advantage of generating less acoustical noise than iron-core coils, they eliminate the potential environmental hazard of spilled oil, and they do not saturate under transient high current fault conditions. This part of the plant will also contain instruments for measurement of direct current and voltage. Special direct current filters are used to eliminate high frequency interference. Such filters are required if

SECTION 10

#1732790627928

228-412: The converter station will require between 40% and 60% of its power rating as reactive power. This can be provided by banks of switched capacitors or by synchronous condensers , or if a suitable power generating station is located close to the static inverter plant, the generators in the power station. The demand for reactive power can be reduced if the converter transformers have on-load tap changers with

247-422: The converter transformers, isolating switches, grounding switches, and instrument transformers for control, measurement and protection. The station will also have lightning arresters for protection of the AC equipment from lightning surges on the AC system. The area required for a converter station is much larger than a conventional transformer, for example a site with a transmission rating of 600 megawatts and

266-513: The floor or hang from insulators from the ceiling. Line commutated converters require voltage from the AC network for commutation, but since the late 1990s, voltage sourced converters have started to be used for HVDC. Voltage sourced converters use insulated-gate bipolar transistors instead of thyristors, and these can provide power to a deenergized AC system. Almost all converters used for HVDC are intrinsically able to operate with power conversion in either direction. Power conversion from AC to DC

285-455: The load current, with a parallel capacitor to form a resonant circuit. In special cases, it may be possible to use exclusively machines for generating the reactive power. This is realized at the terminal of HVDC Volgograd-Donbass situated on Volga Hydroelectric Station . The three-phase alternating current switch gear of a converter station is similar to that of an AC substation. It will contain circuit breakers for overcurrent protection of

304-514: The orders 6 n + 1 and 6 n - 1 produced on the AC side and even harmonics of order 6 n on the DC side. At 12 pulse converter stations, only harmonic voltages or currents of the order 12 n + 1 and 12 n - 1 (on the AC side) or 12 n (on the DC side) result. Filters are tuned to the expected harmonic frequencies and consist of series combinations of capacitors and inductors. Voltage sourced converters generally produce lower intensity harmonics than line commutated converters. As

323-515: The supply of a spare transformer more economical. Converter transformers operate with high flux Power Steps In the Four Steps of the Converter per cycle, and so produce more acoustic noise than normal three-phase power transformers. This effect should be considered in the siting of an HVDC converter station. Noise-reducing enclosures may be applied. When line commutated converters are used,

342-403: The transmission line will use power-line communication techniques for communication and control, or if the overhead line will run through populated areas. These filters can be passive LC filters or active filters, consisting of an amplifier coupled through transformers and protection capacitors, which gives a signal out of phase to the interference signal on the line, thereby cancelling it. Such

361-593: Was named after Anthony Henday, an eighteenth-century trader who worked for the Hudson's Bay Company. 56°30′14″N 94°08′24″W  /  56.50389°N 94.14000°W  / 56.50389; -94.14000 This article about a building or structure in Manitoba is a stub . You can help Misplaced Pages by expanding it . This article about a Canadian power station is a stub . You can help Misplaced Pages by expanding it . HVDC converter station The converter