Direct current ( DC ) is one-directional flow of electric charge . An electrochemical cell is a prime example of DC power. Direct current may flow through a conductor such as a wire, but can also flow through semiconductors , insulators , or even through a vacuum as in electron or ion beams . The electric current flows in a constant direction, distinguishing it from alternating current (AC). A term formerly used for this type of current was galvanic current .

#280719

48-641: ENTSO-E , the European Network of Transmission System Operators , represents 40 electricity transmission system operators (TSOs) from 36 countries across Europe, thus extending beyond EU borders. ENTSO-E was established and given legal mandates by the EU's Third Package for the Internal energy market in 2009, which aims at further liberalising the gas and electricity markets in the EU. Ukrainian Ukrenergo became

96-510: A rectifier , which contains electronic elements (usually) or electromechanical elements (historically) that allow current to flow only in one direction. Direct current may be converted into alternating current via an inverter . Direct current has many uses, from the charging of batteries to large power supplies for electronic systems, motors, and more. Very large quantities of electrical energy provided via direct-current are used in smelting of aluminum and other electrochemical processes. It

144-543: A DC circuit. However, most such circuits have a DC solution. This solution gives the circuit voltages and currents when the circuit is in DC steady state . Such a circuit is represented by a system of differential equations . The solution to these equations usually contain a time varying or transient part as well as constant or steady state part. It is this steady state part that is the DC solution. There are some circuits that do not have

192-407: A DC solution. Two simple examples are a constant current source connected to a capacitor and a constant voltage source connected to an inductor. In electronics, it is common to refer to a circuit that is powered by a DC voltage source such as a battery or the output of a DC power supply as a DC circuit even though what is meant is that the circuit is DC powered. In a DC circuit, a power source (e.g.

240-484: A TSO is an operator that transmits electrical power from generation plants over the electrical grid to regional or local electricity distribution operators. In natural gas business, a TSO receives gas from producers, transports it via pipeline through an area and delivers to gas distribution companies. The United States has similar organizational categories: independent system operator (ISO) and regional transmission organization (RTO). Safety and reliability are

288-453: A battery system to ensure power is maintained for subscriber lines during power interruptions. Other devices may be powered from the telecommunications DC system using a DC-DC converter to provide any convenient voltage. Many telephones connect to a twisted pair of wires, and use a bias tee to internally separate the AC component of the voltage between the two wires (the audio signal) from

336-423: A battery, capacitor, etc.) has a positive and negative terminal, and likewise, the load also has a positive and negative terminal. To complete the circuit, positive charges need to flow from the power source to the load. The charges will then return to the negative terminal of the load, which will then flow back to the negative terminal of the battery, completing the circuit. If either the positive or negative terminal

384-458: A critical issue for transmission system operators, since any failure on their grid or their electrical generation sources might propagate to a very large number of customers, causing personal and property damages. Natural hazards and generation/consumption imbalances are a major cause of concern. To minimize the probability of grid instability and failure, regional or national transmission system operators are interconnected to each other. The role of

432-524: A direct current source . The DC solution of an electric circuit is the solution where all voltages and currents are constant. Any stationary voltage or current waveform can be decomposed into a sum of a DC component and a zero-mean time-varying component; the DC component is defined to be the expected value, or the average value of the voltage or current over all time. Although DC stands for "direct current", DC often refers to "constant polarity". Under this definition, DC voltages can vary in time, as seen in

480-642: A disturbance or outage). The Third Energy Package and Regulation (EC) No 714/2009 on conditions for access to the network for cross-border exchanges in electricity regulation stipulate ENTSO-E's tasks and responsibilities. Regulation (EU) 838/2010 on guidelines relating to the inter-TSO compensation mechanism sets out the methodology by which TSOs receive compensation for the costs incurred in hosting cross-border flows of electricity. Regulation (EU) 347/2013 on guidelines for trans-European energy infrastructure defines European Projects of Common Interest (PCIs) identifies ENTSO-E's ten-year network development plan (TYNDP) as

528-600: A part of the ENTSO-E, while still offering data by their predecessors for public interest. Creation of ENTSO-E was initiated by the adoption of the European Union third legislative package on the gas and electricity markets . In 2003, the European Commission conducted a sector inquiry concerning the competition of electricity market in six European countries. Examining competition in these countries,

SECTION 10

#1732790359281

576-554: Is also used for some railways , especially in urban areas . High-voltage direct current is used to transmit large amounts of power from remote generation sites or to interconnect alternating current power grids. Direct current was produced in 1800 by Italian physicist Alessandro Volta 's battery, his Voltaic pile . The nature of how current flowed was not yet understood. French physicist André-Marie Ampère conjectured that current travelled in one direction from positive to negative. When French instrument maker Hippolyte Pixii built

624-482: Is an AC device which uses a rectifier to produce DC for battery charging. Most highway passenger vehicles use nominally 12  V systems. Many heavy trucks, farm equipment, or earth moving equipment with Diesel engines use 24 volt systems. In some older vehicles, 6 V was used, such as in the original classic Volkswagen Beetle . At one point a 42 V electrical system was considered for automobiles, but this found little use. To save weight and wire, often

672-435: Is commonly found in many extra-low voltage applications and some low-voltage applications, especially where these are powered by batteries or solar power systems (since both can produce only DC). Most electronic circuits or devices require a DC power supply . Domestic DC installations usually have different types of sockets , connectors , switches , and fixtures from those suitable for alternating current. This

720-831: Is defined by the Third Package . ACER develops a framework guideline setting the policy choices for each code. On this basis, the codes are drafted by ENTSO-E in consultation with stakeholders. After ACER's opinion and recommendation for adoption, each code is submitted to the European Commission for approval through the Comitology process , i.e., to be voted on by Member State representatives and thus to become EU law, directly binding and implemented across all Member States. ENTSO-E's Central Information Transparency Platform provides free access to fundamental data and information on pan-European wholesale energy generation, transmission, and consumption. ENTSO-E's R&D Roadmap provides

768-620: Is defined by the European Commission. The certification procedure for transmission system operators is listed in Article 10 of the Electricity and Gas Directives of 2009. Due to the cost of establishing a transmission infrastructure, such as main power lines or gas main lines and associated connection points, a TSO is usually a natural monopoly , and as such is often subjected to regulations. In electrical power business,

816-427: Is disconnected, the circuit will not be complete and the charges will not flow. In some DC circuit applications, polarity does not matter, which means you can connect positive and negative backwards and the circuit will still be complete and the load will still function normally. However, in most DC applications, polarity does matter, and connecting the circuit backwards will result in the load not working properly. DC

864-412: Is distributed to a substation, which utilizes a rectifier to convert the power to direct current. The term DC is used to refer to power systems that use only one electrical polarity of voltage or current, and to refer to the constant, zero-frequency, or slowly varying local mean value of a voltage or current. For example, the voltage across a DC voltage source is constant as is the current through

912-547: Is financed by its members. The TSOs contribute to the budget according to the number of countries and the population served. The highest body of ENTSO-E is the Assembly, which is composed of representatives at CEO level of all the currently 43 members. The ENTSO-E Board is elected every two years from the overall membership and through the Assembly. It includes 12 representatives. The president, vice president, and committee chairs are invited to board meetings. The board coordinates

960-447: Is mostly due to the lower voltages used, resulting in higher currents to produce the same amount of power . It is usually important with a DC appliance to observe polarity, unless the device has a diode bridge to correct for this. Most automotive applications use DC. An automotive battery provides power for engine starting, lighting, the ignition system, the climate controls, and the infotainment system among others. The alternator

1008-485: Is required to maintain a continuous (second-by-second) balance between electricity supply from power stations and demand from consumers, and also ensure the provision of reserves that will allow for sudden contingencies . The system operator achieves this by determining the optimal combination of generating stations and reserve providers for each market trading period, instructing generators when and how much electricity to generate, and managing any contingent events that cause

SECTION 20

#1732790359281

1056-478: Is synchronous within each area, and a disturbance at one single point in the area will be registered across the entire zone. Individual synchronous areas are interconnected through direct current interconnectors . The benefits of synchronous areas include pooling of generation capacities, common provisioning of reserves, both resulting in cost-savings, and mutual assistance in the event of disturbances, resulting in cheaper reserve power costs (for instance in case of

1104-520: Is the basis for the selection of EU projects of common interest (PCIs). The list of PCIs is not fixed by ENTSO-E and is subject to a different process led by the European Commission and EU Member States. The TYNDP is updated every two years. For inclusion in the TYNDP, each project, whether transmission or storage, has to go through a cost–benefit analysis. The benefit analysis methodology is developed by ENTSO-E in consultation with stakeholders and adopted by

1152-409: The transmission grid company, or may be fully independent. They are often wholly or partly owned by state or national governments. In many cases they are independent of electricity generation companies (upstream) and electricity distribution companies (downstream). They are financed either by the states or countries or by charging a toll proportional to the energy they carry. The system operator

1200-660: The 40th member of ENTSO-E on 1 January 2024. On 14 January 2016 TEİAŞ signed an agreement with ENTSO-E to become first observer member, the agreement expired in January 2019. On 13 December 2022 TEİAŞ signed a new Observer Membership Agreement that will run for a period of three years. The geographical area covered by ENTSO-E's member TSOs is divided into five synchronous areas and two isolated systems (Cyprus and Iceland). Synchronous areas are groups of countries that are connected via their respective power systems. The system frequency (50 Hz, with usually very minor deviations)

1248-600: The 40th member of the association on 1 January 2024. On 27 June 2008, 36 European electricity transmission system operators (TSOs) signed in Prague a declaration of intent to create the ENTSO-E. ENTSO-E was established on 19 December 2008 in Brussels by 42 TSOs as a successor of six regional associations of the electricity transmission system operators. ENTSO-E became operational on 1 July 2009. The former associations ETSO, ATSOI, UKTSOA, NORDEL, UCTE and BALTSO became

1296-448: The DC component of the voltage between the two wires (used to power the phone). High-voltage direct current (HVDC) electric power transmission systems use DC for the bulk transmission of electrical power, in contrast with the more common alternating current systems. For long-distance transmission, HVDC systems may be less expensive and suffer lower electrical losses. Applications using fuel cells (mixing hydrogen and oxygen together with

1344-498: The ENTSO-E Transparency Platform. ENTSO‑E does not class as a "public sector body" under the meaning provided in the 2019 Open Data Directive . The ten-year network development plan 2016 (TYNDP) is drafted by ENTSO-E, in close cooperation with stakeholders, under scrutiny of ACER and is finally adopted by the European Commission . It is the only existing pan-European network development plan. It

1392-472: The ENTSO-E vision on grid projects to be carried out by TSOs to meet EU objectives. The roadmap is supported by the annual R&D Implementation Plan, which combines both top-down and bottom-up approaches in meeting the requirements of the roadmap. ENTSO-E publishes annually a R&D Monitoring Report that assesses the progress of TSO-related R&D work. ENTSO-E is an international non-profit association ( AISBL ) established according to Belgian law. ENTSO-E

1440-497: The European Commission. It assesses projects against socio-economic and environmental criteria. ENTSO-E publishes summer and winter adequacy outlooks, as well as a mid-term resource adequacy assessment, the European Resource Adequacy Assessment (ERAA). The seasonal outlooks assess if there is enough generation to cover supply and highlight possibilities for neighbouring countries to contribute to

1488-547: The association. ENTSO-E's Secretariat is based in Brussels. It is headed by the secretary-general and represents ENTSO-E to the European institutions, regulators, and stakeholders. Transmission system operator A transmission system operator ( TSO ) is an entity entrusted with transporting energy in the form of natural gas or electrical power on a national or regional level, using fixed infrastructure . The term

European Network of Transmission System Operators for Electricity - Misplaced Pages Continue

1536-649: The balance between supply and demand to be disrupted. System operations staff undertake this work using sophisticated energy modelling and communications systems. In addition to its roles of real-time dispatch of generation and managing security, the system operator also carries out investigations and planning to ensure that supply can meet demand and system security can be maintained during future trading periods. Examples of planning work may include coordinating generator and transmission outages, facilitating commissioning of new generating plant and procuring ancillary services to support power system operation. A gas TSO works for

1584-521: The basis for the selection of PCIs. ENTSO-E is also mandated to develop a corresponding cost–benefit methodology for the assessment of transmission infrastructure projects. The Transparency Regulation (EU) No. 543/2013   on submission and publication of data in electricity markets makes it mandatory for European Member State data providers and owners to submit fundamental information related to electricity generation, load, transmission, balancing, outages, and congestion management for publication through

1632-407: The circuit voltages and currents are independent of time. A particular circuit voltage or current does not depend on the past value of any circuit voltage or current. This implies that the system of equations that represent a DC circuit do not involve integrals or derivatives with respect to time. If a capacitor or inductor is added to a DC circuit, the resulting circuit is not, strictly speaking,

1680-501: The committees and LRG work and implements Assembly decisions. ENTSO-E has established four specialized committees composed of managers from member TSOs. Each committee leads a number of regional groups and working groups. At the same level as the four committees, the transversal Legal & Regulatory Group advises all ENTSO-E bodies on legal and regulatory issues. In addition, expert groups on data, network codes implementation, and EU affairs provide specific expertise and work products to

1728-576: The development of the grid infrastructure, too. TSOs in the European Union internal electricity market are entities operating independently from the other electricity market players (unbundling). ENTSO-E contained 40 Member TSOs from 36 countries as of January 2024. Due to Brexit three Great Britain based operators left and only Northern Ireland's SONI remains from the UK. On 26 April 2022 Ukrenergo signed an observer membership agreement and became

1776-523: The final report stated serious issues to be solved. It was noticed that the integration between member state's markets is still insufficient. Additionally, the absence of transparently available market information was assessed. As a result, the third legislative package on the EU gas and electricity markets was adopted by the European Commission in September 2007. According to its website, "ENTSO-E promotes closer cooperation across Europe’s TSOs to support

1824-654: The first dynamo electric generator in 1832, he found that as the magnet used passed the loops of wire each half turn, it caused the flow of electricity to reverse, generating an alternating current . At Ampère's suggestion, Pixii later added a commutator , a type of "switch" where contacts on the shaft work with "brush" contacts to produce direct current. The late 1870s and early 1880s saw electricity starting to be generated at power stations . These were initially set up to power arc lighting (a popular type of street lighting) running on very high voltage (usually higher than 3,000 volts) direct current or alternating current. This

1872-567: The focal point for all technical, market and policy issues relating to TSOs and the European network, interfacing with power system users, EU institutions, regulators and national governments." TSOs are responsible for the bulk transmission of electric power on the main high voltage electric networks. TSOs provide grid access to the electricity market players (i.e., generating companies, traders, suppliers, distributors, and directly connected customers) according to non-discriminatory and transparent rules. In many countries, TSOs are in charge of

1920-506: The functioning of the internal market and cross-border trade for gas and to ensure the optimal management, coordinated operation and sound technical evolution of the natural gas transmission network. Some gas TSOs also provide the marketplace for gas trading. Direct current The abbreviations AC and DC are often used to mean simply alternating and direct , as when they modify current or voltage . Direct current may be converted from an alternating current supply by use of

1968-418: The generation/demand balance in critical situations in a specific country. The ERAA analyses resource adequacy on the decade ahead, accounting for investment and retirement decisions. ENTSO-E's network codes are binding pan-European rules drafted by ENTSO-E in consultation with stakeholders, with guidance from ACER . Network codes are grouped in three areas: The drafting and adoption process of network codes

European Network of Transmission System Operators for Electricity - Misplaced Pages Continue

2016-573: The implementation of EU energy policy and achieve Europe’s energy & climate policy objectives, which are changing the very nature of the power system. The main objectives of ENTSO-E centre on the integration of renewable energy sources (RES) such as wind and solar power into the power system, and the completion of the internal energy market (IEM), which is central to meeting the European Union’s energy policy objectives of affordability, sustainability and security of supply. [...] ENTSO-E aims to be

2064-512: The metal frame of the vehicle is connected to one pole of the battery and used as the return conductor in a circuit. Often the negative pole is the chassis "ground" connection, but positive ground may be used in some wheeled or marine vehicles. In a battery electric vehicle , there are usually two separate DC systems. The "low voltage" DC system typically operates at 12V, and serves the same purpose as in an internal combustion engine vehicle. The "high voltage" system operates at 300-400V (depending on

2112-428: The raw output of a rectifier or the fluctuating voice signal on a telephone line. Some forms of DC (such as that produced by a voltage regulator ) have almost no variations in voltage , but may still have variations in output power and current. A direct current circuit is an electrical circuit that consists of any combination of constant voltage sources, constant current sources, and resistors . In this case,

2160-416: The system operator in a wholesale electricity market is to manage the security of the power system in real time and co-ordinate the supply of and demand for electricity, in a manner that avoids fluctuations in frequency or interruptions of supply. The system operator service is normally specified in rules or codes established as part of the electricity market. The system operator function may be owned by

2208-464: The vehicle), and provides the power for the traction motors . Increasing the voltage for the traction motors reduces the current flowing through them, increasing efficiency. Telephone exchange communication equipment uses standard −48 V DC power supply. The negative polarity is achieved by grounding the positive terminal of power supply system and the battery bank. This is done to prevent electrolysis depositions. Telephone installations have

2256-406: Was followed by the widespread use of low voltage direct current for indoor electric lighting in business and homes after inventor Thomas Edison launched his incandescent bulb based electric " utility " in 1882. Because of the significant advantages of alternating current over direct current in using transformers to raise and lower voltages to allow much longer transmission distances, direct current

2304-477: Was replaced over the next few decades by alternating current in power delivery. In the mid-1950s, high-voltage direct current transmission was developed, and is now an option instead of long-distance high voltage alternating current systems. For long distance undersea cables (e.g. between countries, such as NorNed ), this DC option is the only technically feasible option. For applications requiring direct current, such as third rail power systems, alternating current